Multipair Individual/Overall Screen with Armor
Application :
- These cables are used in thermocouple circuits, petrochemical plants, utilities and industrial plants.
Specification :
-
Conductor Solid Type applicable KX, EX, JX, TX, NX, KCA, KCB, RCA, RCB, SCA, RCB, BC Insulation PVC, PE, XLPE or LSZH thermoplastic material Individual screen 24 μm aluminium / PETP tape over solid tinned copper drain wire, 0.6 mm Wrapping At least 1 layer of plastic tape Overall screen 24 μm aluminium / PETP tape over 7-stranded tinned copper drain wire, 0.5 mm² Bedding PE, PVC or LSZH thermoplastic material Armor Galvanized round steel wires Outer sheath PVC or LSZH thermoplastic material Color code According to IEC 60584-3 Flame retardancy IEC 60332-1 Flame propagation IEC 60332 cat. C Temperature range -30°C up to 70°C during operation. -5°C up to 50°C during installation -
TX IS/OS & armored
0.5 mm² :
-
Conductor Size No. of Pairs Insulation Thickness (mm) Bedding Thickness (mm) Diameter of Armor Wire (mm) Outer Sheath Thickness (mm) Nominal O.D. (mm) Weight* (kg/km) 0.5 2 0.4 0.9 0.9 1.4 13.5 314 0.5 4 0.4 1.1 0.9 1.4 15.2 393 0.5 6 0.4 1.2 0.9 1.5 17.6 497 0.5 8 0.4 1.2 0.9 1.5 18.4 567 0.5 10 0.4 1.2 1.25 1.6 21.0 832 0.5 12 0.4 1.2 1.25 1.6 21.7 893 0.5 16 0.4 1.3 1.25 1.7 24.2 1057 0.5 20 0.4 1.3 1.25 1.7 26.0 1196 0.5 24 0.4 1.3 1.25 1.8 27.8 1397
0.8 mm² :
-
Conductor Size No. of Pairs Insulation Thickness (mm) Bedding Thickness (mm) Diameter of Armor Wire (mm) Outer Sheath Thickness (mm) Nominal O.D. (mm) Weight* (kg/km) 0.8 2 0.4 0.9 0.9 1.4 14.2 351 0.8 4 0.4 1.1 0.9 1.5 16.3 460 0.8 6 0.4 1.2 0.9 1.5 18.7 576 0.8 8 0.4 1.2 0.9 1.6 19.7 675 0.8 10 0.4 1.2 1.25 1.6 22.4 966 0.8 12 0.4 1.3 1.25 1.7 23.6 1059 0.8 16 0.4 1.3 1.25 1.7 25.8 1246 0.8 20 0.4 1.3 1.25 1.8 28.0 1439 0.8 24 0.4 1.5 1.25 1.8 30.3 1667
1.0 mm² :
-
Conductor Size No. of Pairs Insulation Thickness (mm) Bedding Thickness (mm) Diameter of Armor Wire (mm) Outer Sheath Thickness (mm) Nominal O.D. (mm) Weight* (kg/km) 1.0 2 0.4 1.1 0.9 1.4 15.0 374 1.0 4 0.4 1.1 0.9 1.5 16.7 495 1.0 6 0.4 1.2 0.9 1.6 19.4 636 1.0 8 0.4 1.2 1.25 1.6 21.0 884 1.0 10 0.4 1.2 1.25 1.7 23.3 1064 1.0 12 0.4 1.3 1.25 1.7 24.3 1153 1.0 16 0.4 1.3 1.25 1.7 26.7 1365 1.0 20 0.4 1.5 1.25 1.8 29.4 1582 1.0 24 0.4 1.5 1.6 1.9 32.3 2098
1.3 mm² :
-
Conductor Size No. of Pairs Insulation Thickness (mm) Bedding Thickness (mm) Diameter of Armor Wire (mm) Outer Sheath Thickness (mm) Nominal O.D. (mm) Weight* (kg/km) 1.3 2 0.4 1.1 0.9 1.5 16.5 415 1.3 4 0.4 1.2 0.9 1.5 18.6 545 1.3 6 0.4 1.2 1.25 1.6 22.2 853 1.3 8 0.4 1.2 1.25 1.6 23.3 980 1.3 10 0.4 1.3 1.25 1.7 26.1 1183 1.3 12 0.4 1.3 1.25 1.7 27.0 1288 1.3 16 0.4 1.3 1.25 1.8 30.0 1553 1.3 20 0.4 1.5 1.25 1.9 33.2 1806 1.3 24 0.4 1.5 1.6 1.9 36.1 2358
1.5 mm² :
-
Conductor Size No. of Pairs Insulation Thickness (mm) Bedding Thickness (mm) Diameter of Armor Wire (mm) Outer Sheath Thickness (mm) Nominal O.D. (mm) Weight* (kg/km) 1.5 2 0.5 1.1 0.9 1.5 17.6 461 1.5 4 0.5 1.2 0.9 1.5 19.9 611 1.5 6 0.5 1.2 1.25 1.6 23.8 957 1.5 8 0.5 1.3 1.25 1.7 25.4 1119 1.5 10 0.5 1.3 1.25 1.7 28.1 1336 1.5 12 0.5 1.3 1.25 1.7 29.2 1459 1.5 16 0.5 1.5 1.25 1.9 33.2 1783 1.5 20 0.5 1.5 1.6 1.9 36.7 2308 1.5 24 0.5 1.7 1.6 2.0 39.8 2706 - *The number here is just approx. weight. It changes according to the insulation material and the conductor used in different type of extension cable and compensating cable.